Automation – Lenze EDS4900U-REG User Manual
Page 266

Automation
12-6
48XX/49XXSHB0399
C392 field current set-value
Note!
The field current cannot be reduced more than to the minimum field current set
under C231. If the controller is in field-weakening operation, this range cannot be
left by setting a higher field current set-value.
Display of the field current set-value.The figure 2
14
= 16384 corresponds to 100%
of the rated value under C083. The field current set-vlaue can be assigned to a
process input word so that the set-value can be controlled via the fieldbus system.
C393 additional set-value
Display of the additional set-value for the speed controller. The figure 2
14
= 16384
corresponds to 100% of the maximum additional set-value. The information is the
same as under C049.
Code
Name
Possible settings
Code
Name
Lenze Selection
Info
C380*
n
set
speed
-16384
{1}
16384
High precision set-value input:
16384
100%under C046
Input only via interface
C381*
n
set
at
n controller
-32767
{1}
32767
High precision set-value display:
Input of the speed controller
16384
100%under C050.
Input only via interface.
C382*
Actual
speed
-32767
{1}
32767
High precision display: actual speed value
16384
n
max
under C011.
Input only via interface.
C387*
Torque limit
-16384
{1}
16384
High precision torque set-value input:
16384
100%under C047.
Input only via interface.
C388*
Torque
setpoint
-16384
{1}
16384
High precision torque set-value display:
16384
100%under C056.
Input only via interface.
C391*
Actual
phase
0
{1}
65535
High precision display of the actual phase
value if resolver or incrmental encoder
operate as feedback system:
16384
360 1 revolution
Input only via interface.
C392*
Field
current
set-value
0
{1}
16384
High precision display of the field current
set-value:
16384
I
Frated
under C083.
Input only via interface.
C393*
Additional
set-value
-16384
{1}
16384
High precision additional set-value display:
16384
100%under C049.
Display only via interface.