Commissioning – Lenze EDS4900U-REG User Manual
Page 83

Commissioning
5-7
48XX/49XXSHB0399
With the configurations C005 = -X2- or -X3- and activated angle controller
(C254 > 0), the drive will be decelerated to speed = 0 and angle-controlled
(drift-free). The drive can thus generate its maximum torque (independently of the
current limit C022, C023).
Code
Name
Possible settings
Code
Name
Lenze Selection
Info
C105
Decele-
ration time
for quick
stop
0.00s 0 s
{0.01 s}
1 s
1 s
{0.1s}
10s
10 s
{1 s}
100 s
100 s
{10 s}
990 s
Time referred to the speed change
0...n
max
( Configuration possibilities for the selection of the direction of rotation and
quick stop
Operating
mode
Setpoint to
X1/8
X2/21
X2/22
C041
C042
Direction of
rotation
(View
towards
motor shaft)
Terminal
control
positive
HIGH
LOW
-0-
-0-
cw
control
negative
LOW
HIGH
-1-
-0-
C041 and
positive
LOW
HIGH
-1-
-0-
ccw
C041 and
C042 display
the stat s of
negative
HIGH
LOW
-0-
-0-
the status of
terminals
pos. / neg.
HIGH
HIGH
-0- / -1-
-0-
unchanged
terminals
X2/21 and
X2/22
pos. / neg.
LOW
LOW
-0- / -1-
-1-
Quick stop
active
Keypad /
LECOM
positive
HIGH/LOW
LOW/HIGH
-0-
-0-
cw
C041 and
C042
negative
HIGH/LOW
LOW/HIGH
-1-
-0-
C042
determine the
direction of
rotation or
positive
HIGH/LOW
LOW/HIGH
-1-
-0-
ccw
rotation or
quick stop, in
addition LOW
i
l X2/21
negative
HIGH/LOW
LOW/HIGH
-0-
-0-
signal X2/21
and X2/22
activates quick
stop.
pos. / neg.
LOW
LOW
-0- / -1-
-1-
Quick stop
active
Show/Hide Bookmarks