Troubleshooting and fault elimination – Lenze EDS4900U-REG User Manual
Page 250

Troubleshooting and fault elimination
8-5
48XX/49XXSHB0399
Display
Remedy
Cause
OUE
Mains overvoltage
Mains voltage > 460V or 550V (500V variant) Reduce mains voltage with a preconnected
transformer or
use a controller with a higher mains
connection voltage.
P03
Following error
Angle difference between set and actual
position is larger than the following error limit
set under C255
Drive cannot follow the digital frequency (I
max
limit)
Extend following limit with C255
Switch-off monitoring if required (C119/C120)
Enable drive (Ctrl. enable)
Check drive dimensioning
P13
Angle overflow
Angle controller limit reached
Drive cannot follow the digital frequency (I
max
limit)
Enable drive
Check drive dimensioning
PER
Program interference
A fault in the program sequence was detected Send controller with data (on diskette) to
Lenze
PR
Parameter reset
After switching on, a change in the software
version has been detected.
Automatic loading of factory setting.
Set the required parameters and save settings
under C003.
PR1 ... PR4 Parameter set error
Fault when reading a parameter set
CAUTION:
The factory setting is loaded automatically
Set the required parameters and save settings
under C003.
Sd1
Tacho fault
Short circuit or interruption of tacho cable
Check tacho cables for short-circuit or
interruption and remove fault
Sd2
Resolver fault
Resolver cable interrupted
Check resolver cable for open circuit
Check resolver
Acknowledge fault by mains switching
Sd3
Encoder fault at Dig_In 1 Incremental encoder or digital frequency cable
interrupted at X5
Input X5 PIN 8 not assigned
Check cable for open circuit
Assign input X5 PIN 8 with encoder potential
or switch off monitoring (C119 / C120)
Sd4
Encoder fault at Dig_In 2 Incremental encoder or digital frequency cable
interrupted at X9
Input X9 PIN 8 not assigned
Assign input X9 PIN 8 with encoder potential
or switch off monitoring (C119 / C120)
Sd5
Master current
interrupted
Interruption of the master current selection,
I
master
< 2mA
with master current selection 4...20mA, C034
= -1-
Remove interruption of the set-value cable or
select master selection 0...20 mA under C034
= -0-
SP
Wrong signal source
polarity
Tacho, resolver or fieldbus connection are
interchanged
Change tacho, resolver or fieldbus connection
U15
15V supply interfered Overload / short-circuit terminal 20
Check load at terminal 20
15 V supply defective
Return controller