5 control of a holding brake, Configuration – Lenze EDS4900U-REG User Manual
Page 153

Configuration
7-62
48XX/49XXSHB0399
7.4.5
Control of a holding brake
Purpose
Control singal for holding brakes in:
( hoists
( travelling drives
( active loads
Code
Name
Possible settings
Code
Name
Lenze Selection
Info
C019*
Threshold
n
act
= 0
50 rpm 0 rpm
{1 rpm}
5000 rpm
If the acutal speed falls below the
threshold, the corresponding output will be
activated.
C195*
Delay
between
’engage
brake’ and
controller
inhibit
9999 s 0.00s
{0.01 s}
1s
1s
{0.1s}
10s
10s
{1s}
250s
9999 s
Delay between signal ’engage brake’ and
automatic controller inhibit
9999 s:
Unlimited delay, controller will not be
inhibited.
C196*
Delay
between
’setpoint
integrator
free’ and
quick stop
0.00s 0.00 s
{0.01 s}
1 s
1s
{0.1s}
10s
10s
{1s}
100s
100s
{10s}
250s
Delay between reset of the quick stop
function and enable of the main setpoint
integrator
[C197*] Sign of the
torque
selection
0
-0-
Sign is determined by the torque setpoint
-1-
positive sign
-2-
negative sign
Sign of the torque selection between reset
of QSP and enable of the setpoint
integrators
C244*
Threshold
I
A
> I
x
10%
0 % I
Amax
{0.1% I
Amax
} + 100 % I
Amax
I
A
> I
x
Reference, rated controller current
(armature)
C245*
Threshold
I
F
> I
x
10%
0 % I
Fmax
{0.1% I
Fmax
}
+ 100 % I
Fmax
I
F
> I
x ,
Reference, rated controller current (field)
C317*
Time delay
for the
reduced
field current
60 s
0.0 s
{0.1 s}
10 s
10 s
{1 s}
100 s
100 s
{10 s}
3600 s
Time which is required to activate the
reduced field current after inhibiting the
controller.
C318*
¤ Activate
field current
reduction
0
-0-
Field current reduction function is off
-1-
Field current reduction function is switched on
The function for the control of a holding brake only makes sense with the
configurations C005 = -1X- and -5X-. The brake control is always derived from the
QSP function.