3 connection, Installation – Lenze EDS4900U-REG User Manual
Page 43

Installation
4-5
48XX/49XXSHB0399
4.3
Connection
Connection between controller and motor
Lenze controller
Motor (to DIN 42017/VDE 0530 part 8)
Function
Terminal
Terminal
Others
Motor type
Armature voltage
Excitation voltage
+
-
+
-
A
B
I
K
1B1
2B2
F1
F2
A1
B2, A2
F5, (for higher connection voltages)
F2
DC motor
uncompensated with
commutating winding
Armature voltage
Excitation voltage
+
-
+
-
A
B
I
K
1C1
2C2
F1
F2
A1
C2
F5, (for higher connection voltages)
F2
DC motor
compensated with
commutating winding
Armature voltage
+
-
A
B
A1
A2
Permanent-magnet
motor
DC tacho
+
-
3
4
2A1
2A2
Temp. switch
S1, S2
Thermal contact
T1, T2
Screw-tightening torques
Type
4902
4903 - 4904
4905 - 4907
4X08 - 4X09
4X11 - 4X13
L1, L2, L3, A, B
0.5 ... 0.6 Nm
2.0 ... 2.4 Nm
37 Nm
1)
64 Nm
1)
A, B
0.5 ... 0.6 Nm
2.0 ... 2.4 Nm
37 Nm
1)
15 ... 20 Nm
64 Nm
L1.1, L3.1, I, K
0.5 ... 0.6 Nm
1.2 ... 1.5 Nm
L1.2, L2.2, L3.2
0.5 ... 0.6 Nm
L1.3, L2.3, L3.3, 86 - 89
-
0.5 ... 0.6 Nm
Terminal strip X1 - X4
0.5 ... 0.6 Nm
1)
Rated tightening torque for the connection of terminal ends to busbars
(VDE 0220 part 1/11.71)
When continued with busbar see DIN 43673 part 1/02.82
The following circuit diagrams show the electrical wiring of the power connections.
Show/Hide Bookmarks