Configuration – Lenze EDS4900U-REG User Manual
Page 223

Configuration
7-132
48XX/49XXSHB0399
Code
Possible settings
Name
Code
Info
Selection
Lenze
Name
C123
Current
threshold for
blocking
protection for
C124
0.95
I
rated
0 A
{0.1A}
100 A
100 A
{1 A}
3600 A
Rated current depends on the controller:
0 ... 87A
(4902)
0 ... 135A
(4903)
0 ... 270A
(4904)
0 ... 450A
(4905)
0 ... 720A
(4906)
0 ... 900A
(4907)
0 ... 1200A
(4X08)
0 ... 1800A
(4X09)
0 ... 2520A
(4X11)
0 ... 3600A
(4X12)
0 ... 4050A
(4X13)
See motor nameplate
C124*
Blocking time
60 s
1 s
{1 s}
100 s
Motor standstill time until TRIP is set
C125*
¤ Change of baud
rate for
interface
0
-0-
9600 baud
-1-
4800 baud
-2-
2400 baud
-3-
1200 baud
C126*
Delay
(Monitoring ser.
interface)
3000 s 0.2 s
{0.1 s}
10 s
10 s
{1 s}
100 s
100 s
{10 s}
3600 s
C128*
Delay for C116
0.000 s 0.000 s
{0.001 s}
240.000 s
Signal delay times for FDO 1...5 and relay
output.
C130*
Enable
additional T
i
times
0
-0-
T
ir
(C012) / T
if
(C013) active
-1-
T
ir1
/ T
if1
active
...
-15-
T
ir15
/ T
if15
active
If the T
i
times are enabled via terminal,
C130 is for display only.
C131*
¤ Ramp function
generator STOP
0
-0-
Enable ramp function generator
-1-
Stop ramp function generator
If ramp function generator STOP (main
setpoint) is enabled via terminal, C131 is
for display only.
C132*
¤ Ramp function
generator input
= 0
0
-0-
Enable mains setpoint at RFG input
-1-
Ramp function generator input = 0
[C134*] Ramp function
generator
characteristic
0
-0-
linear characteristic
-1-
S-shaped characteristic
C136*
FDI state
Bit
Free digital input
0
FDI 1
...
3
FDI 4
4
FDI 5
Only readable via LECOM. C136 indicates
the states of the digital inputs as a
decimal or binary value.The change of
polarity under C114 is considered in
C136.