Installation – Lenze EDS4900U-REG User Manual
Page 57

Installation
4-19
48XX/49XXSHB0399
Digital inputs
Name
Terminal
Use
(factory setting)
Level for activation
Programming
see chapter
20
Voltage supply 15V, 100mA
CW
21
Removal of quick stop, CW rotation
HIGH
CCW
22
Remove quick stop, CCW rotation
HIGH
1
28
Controller enable - Ctrl. enable
HIGH
2
E1
Freely assignable input
(TRIP set)
HIGH
3
E2
Freely assignable input
(TRIP reset)
HIGH
4
E3
Freely assignable input
(Inhibit additional setpoint)
HIGH
5
E4, E5
Freely assignable input
(Enable JOG values, three JOG values)
HIGH
Digital outputs
Name
Terminal
Use
(factory setting)
Message
Programming
see chapter
1)
2)
39
Ground of the digital inputs and outputs, external GND
40
Internal ground, GND
6
41
TRIP
HIGH
LOW
7
44
Ready for operation
- RDY
HIGH
HIGH
8
45
Pulse inhibit
- IMP
HIGH
LOW
9
A1
Freely assignable output
(n
act
< n
x
)
HIGH
LOW
10
A2
Freely assignable output
(n-controller = M
max
)
LOW
HIGH
11
A3
Freely assignable output
(Setpoint reached, RFG
output
= RFG
input
)
HIGH
HIGH
12
A4
Freely assignable output
(n
act
= 0)
HIGH
LOW
13
A5
Freely assignable output
(n
act
= n
set
)
HIGH
HIGH
59
Supply input of the digital outputs:
24 V external or 15 V internal
1) Message in stationary controller operation
2) Message, if the function is active
Show/Hide Bookmarks