3 fault messages, 1 causes and remedies, Causes and remedies – Lenze ECSCMxxx User Manual
Page 270: 270), the rotor position could not, Troubleshooting and fault elimination, Fault messages causes and remedies

Troubleshooting and fault elimination
Fault messages
Causes and remedies
l
270
EDBCSXM064 EN 11.0
11.3
Fault messages
11.3.1
Causes and remedies
I
Tip!
When the fault messages are retrieved via the MotionBus/system bus (CAN),
the fault messages are displayed as numbers (see column "Fault message ˘
No." in the following table).
Fault message
Description
Cause
Remedy
No.
Display
−−−
−−−
No fault
−
−
0011
OC1
Short circuit of motor cable
Short circuit
l
Search for cause of short
circuit.
l
Check motor cable.
Excessive capacitive charging
current in the motor cable.
Use motor cable which is shorter
or of lower capacitance.
0012
OC2
Motor cable earth fault
One of the motor phases has
earth contact.
l
Search for cause of short
circuit.
l
Check motor cable.
0015
OC5
I x t overload TRIP (axis
module, fix 100 %)
Current overload of the axis
module, e.g. by:
l
frequent and too long
acceleration processes
l
continuous overload with
I
motor
> 1.05 x I
Nx
Check drive dimensioning.
0016
OC6
I
2
x t overload TRIP (motor, C0120) Current overload of the motor,
e.g. due to:
l
frequent or too long
acceleration processes
l
impermissible continuous
current
l
Check drive dimensioning.
l
Check setting of C0120.
x017
OC7
I x t overload warning (axis
module, C0123)
Current overload of the axis
module > C0123 (e.g. due to
frequent or too long acceleration
phases)
l
Check drive dimensioning.
l
Check setting of C0123.
x018
OC8
I
2
x t overload warning
(motor, C0127)
Current overload of the motor
> C0127 (e.g. due to frequent or
too long acceleration phases)
l
Check drive dimensioning.
l
Check setting of C0127.
1020
OU
Overvoltage in DC bus
Braking energy is too high.
(DC−bus voltage is higher than set
in C0173.)
l
Use braking unit or
regenerative module.
l
Check dimensioning of the
brake resistance.
1030
LU
Undervoltage in DC bus
DC−bus voltage is lower than
specified under C0174.
l
Check mains voltage.
l
Check power supply module.
x032
LP1
Motor phase failure
A current−carrying motor phase
has failed.
l
Check motor.
l
Check motor cable.
l
Switch off monitoring
(C0597 = 3).
The current limit value is set too
low.
l
Set higher current limit value
via C0599.
x041
AP1
Internal fault
Contact Lenze.
x: 0 = TRIP, 1 = Message, 2 = Warning, 3 = FAIL−QSP