3 configuring monitoring functions, 1 monitoring times for process data input objects, Configuring monitoring functions – Lenze ECSCMxxx User Manual
Page 225: Monitoring times for process data input objects, Monitoring functions

Monitoring functions
Configuring monitoring functions
Monitoring times for process data input objects
l
225
EDBCSXM064 EN 11.0
9.3
Configuring monitoring functions
9.3.1
Monitoring times for process data input objects
Fault message
Monitoring function
System variable
Possible response
TRIP
Messag
e
Warnin
g
Off
x062
CE1
Communication error at the
process data input object
CAN1_IN
CAN_bCe1CommErrCanIn1_b
ь
ь
·
x063
CE2
Communication error at the
process data input object
CAN2_IN
CAN_bCe2CommErrCanIn2_b
ь
ь
·
x064
CE3
Communication error at the
process data input object
CAN3_IN
CAN_bCe3CommErrCanIn3_b
ь
ь
·
x065
CE4
BUS−OFF state of the CAN bus
at interface X4 (CAN)
CAN_bCe4BusOffState_b
ь
ь
·
x122
CE11
Communication error at the
process data input object
CANaux1_IN
CANaux_bCe1CommErrCanIn1_
b
ь
ь
·
x123
CE12
Communication error at the
process data input object
CANaux2_IN
CANaux_bCe2CommErrCanIn2_
b
ь
ь
·
x124
CE13
Communication error at the
process data input object
CANaux3_IN
CANaux_bCe3CommErrCanIn3_
b
ь
ь
·
x125
CE14
BUS−OFF state of the CAN bus
at interface X14 (CAN−AUX)
CANaux_bCe4BusOffState_b
ь
ь
·
· Default setting
üSetting possible
Each process data input object can monitor whether a telegram has been received within
a specified time. As soon as a telegram arrives, the corresponding monitoring time
(C0357/C02457) is restarted ("retriggerable monoflop" function).
Code
Possible settings
IMPORTANT
No.
Designation
Lenze/
{Appl.}
Selection
C0357
Monitoring time for CAN1...3_IN
(CAN bus interface X4)
^ 225
1 CE monit time
3000
1
{1 ms}
65000 CE1 monitoring time
2 CE monit time
3000
CE2 monitoring time
3 CE monit time
3000
CE3 monitoring time