2.12.17.10 OH4 − heatsink temperature monitoring (adjustable)

This monitoring function protects the drive controller.

Error

Monitoring function

System variable

Possible responses

No.

Display

TRIP

Message

Warning

FAIL−QSP

Off

x054 OH4

Heatsink temperature (adjustable)

MCTRL_bKuehlGreaterC0122_b

·

ü

· Lenze setting

ü Setting possible

This monitoring function is designed as an early warning stage before final disconnection of the drive
controller by means of TRIP (OH) via the monitoring function "heatsink temperature (fixed)".

(

^ 2−84)

·

With this function the process can be influenced to avoid a switch−off of the controller at an
unfavourable moment.

·

Furthermore, for instance, additional fans, which would cause an unacceptable noise in
continuous operation, can also be switched on and off.

MCTRL_bKuehlGreaterC0122_b is derived from a comparator with hysteresis.

·

The operating threshold is set under C0122.

·

Hysteresis is 5 K (fixed), i. e. monitoring is reset at 5 K below the operation threshold that has
been set.

·

The response is set under C0582.

Code

LCD

Possible settings

IMPORTANT

Lenze

Selection

C0122 OH4 limit

85

Temperature threshold for heatsink
temperature prewarning
"Tht > C0122" (fault OH4)

45

{1 °C}

85

C0582 MONIT OH4

2

Configuration of monitoring

2

Warning

3

Off