MCTRL_MotorControl (node number 131)

9300 Servo PLC

System blocks

2−94

L

9300 Servo PLC EN 5.1

2.12.17.19 NMAX − speed monitoring (maximum speed exceeded)

This monitoring function monitors the process.

Error

Monitoring function

System variable

Possible responses

No.

Display

TRIP

Message

Warning

FAIL−QSP

Off

x200 NMAX

Maximum speed exceeded

MCTRL_bNmaxFault_b

·

· Lenze setting

ü Setting possible

The monitoring responds when the current speed exceeds the upper speed limit of the system or the
double value of C0011 (n

max

).

Stop!

·

For active loads (e. g. hoists) ensure torque−free operation of the drive. Special
system−specific measures are required!

·

If the actual speed value encoder fails, the monitoring may fail to respond.

·

The upper system speed is set under C0596:

Code

LCD

Possible settings

IMPORTANT

Lenze

Selection

C0596 NMAX limit

5500

Monitoring configuration: Max. speed
of the machine

0

{1 rpm}

16000