beautypg.com

Touch probe (tp), 15 touch probe (tp), 9300 servo plc – Lenze DDS Target 9300 Servo PLC V8.x User Manual

Page 72: System blocks

background image

2.12

MCTRL_MotorControl (node number 131)

9300 Servo PLC

System blocks

2−66

L

9300 Servo PLC EN 5.1

2.12.15

Touch probe (TP)

Process: The current phase value (digital frequency input value) is saved by a quick interrupt in the
operating system when a signal change occurs at the TP activating input (e.g. X5/E4).

MCTRL_dnActIncLastScan_p

TP



j

Fig. 2−26

Function chart of a TP

 Time−equidistant start of an interval task
j Angle signal

Touch probe configuration

Code

LCD

Possible settings

IMPORTANT

Lenze

Selection

C0910 TP Delay

0

Touch probe delay

·

Compensation of delay times of
the TP signal source at X5/E4

−32767

{1 inc}

32767

C0911 MCTRL TP sel

0

Touch probe selection

0

Touch probe via zero pulse

1

Touch probe through digital input X5/E4

C0912 MCTRL TP EDGE

0

Touch probe activation

·

For touch probe via digital input
X5/E4
(C0911 = 1)

0

Rising edge TP2

1

Falling edge TP2

·

The feedback system generating the zero pulse is set under C0490.

(

^ 2−65)