9300 servo plc, System blocks – Lenze DDS Target 9300 Servo PLC V8.x User Manual
Page 30
![background image](/manuals/566017/30/background.png)
2.4
AIF_IO_Management (node number 161)
9300 Servo PLC
System blocks
2−24
L
9300 Servo PLC EN 5.1
System variables
Variable
Data type
Signal type
Address
Display code
Display
format
Notes
AIF_bCe0CommErr_b
Bool
binary
%IX161.0.0
Communication error "CE0"
AIF_bFieldBusStateBit0_b
%IX161.1.0
Error number − bit 0
AIF_bFieldBusStateBit1_b
%IX161.1.1
Error number − bit 1
AIF_bFieldBusStateBit2_b
%IX161.1.2
Error number − bit 2
AIF_bFieldBusStateBit3_b
%IX161.1.3
Error number − bit 3
AIF_bFieldBusStateBit4_b
%IX161.1.4
Error number − bit 4
AIF_bFieldBusStateBit5_b
%IX161.1.5
Error number − bit 5
AIF_bFieldBusStateBit6_b
%IX161.1.6
Error number − bit 6
AIF_bFieldBusStateBit7_b
%IX161.1.7
Error number − bit 7
AIF_bFieldBusStateBit8_b
%IX161.1.8
Error number − bit 8
AIF_bFieldBusStateBit9_b
%IX161.1.9
Error number − bit 9
AIF_bFieldBusStateBit10_b
%IX161.1.10
Error number − bit 10
AIF_bFieldBusStateBit11_b
%IX161.1.11
Error number − bit 11
AIF_bFieldBusStateBit12_b
%IX161.1.12
Error number − bit 12
AIF_bFieldBusStateBit13_b
%IX161.1.13
Error number − bit 13
AIF_bFieldBusStateBit14_b
%IX161.1.14
Error number − bit 14
AIF_bFieldBusStateBit15_b
%IX161.1.15
Error number − bit 15
Codes
Code
LCD
Possible settings
Info
Lenze
Selection
C0126 MONIT CE0
3
Configuration for communication
error "CE0" with automation
interface
0
TRIP
2
Warning
3
Off
C2121 AIF: state
G
AIF−CAN: Status
·
Detailed information can be
found in the documentation for
the corresponding
communication module.
0
{dec}
255
Decimal value is bit−coded:
Bit 0
XCAN1_IN monitoring time
Bit 1
XCAN2_IN monitoring time
Bit 2
XCAN3_IN monitoring time
Bit 3
XCAN bus−off
Bit 4
XCAN operational
Bit 5
XCAN pre−operational
Bit 6
XCAN warning
Bit 7
Internally assigned