Analog2_io (node number 12), Inputs_analog2 (analog input), Outputs_analog2 (analog output) – Lenze DDS Target 9300 Servo PLC V8.x User Manual
Page 34: 9300 servo plc, 6 analog2_io (node number 12), System blocks, 1 inputs_analog2 (analog input), 2 outputs_analog2 (analog output)
2.6
ANALOG2_IO (node number 12)
9300 Servo PLC
System blocks
2−28
L
9300 Servo PLC EN 5.1
2.6
ANALOG2_IO (node number 12)
2.6.1
Inputs_ANALOG2 (analog input)
The input is the interface for differential analog signals between terminals X6/3, 4.
AIN2_nIn_a
Inputs_ANALOG2
C0405
3
4
X6
Fig. 2−11
Inputs_ANALOG2
System variables
Variable
Data type
Signal type
Address
Display
code
Display
format
Note
AIN2_nIn_a
Integer
Analog
%IW12.0
C0405
dec [%]
Analog input 2
Terminal assignment
Terminal
Use
Measuring range
X6/3, 4
Differential input for master voltage
(no effect of jumper X3)
Level:
Resolution:
Scaling:
−10 V ... +10 V
5 mV (11 bits + sign)
±10 V º ±16384 º ±100 %
2.6.2
Outputs_ANALOG2 (analog output)
The output can be used as a monitor output. Internal analog signals can be output as voltage signals
via terminal X6/63 and used, for instance, as display values or setpoints for slave drives.
Outputs_ANALOG2
AOUT2_nOut_a
C0439
63
X6
Fig. 2−12
Outputs_ANALOG2
System variables
Variable
Data type
Signal type
Address
Display
code
Display
format
Note
AOUT2_nOut_a
Integer
Analog
%QW12.0
C0439
dec [%]
Analog output 2
Terminal assignment
Terminal
Use
Measuring range
X6/63
Analog output 2 (monitor 2)
Level:
Resolution:
Scaling:
−10 V ... +10 V (max. 2 mA)
20 mV (9 bits + sign)
±10 V º ±16384 º ±100 %
X6/7
Internal ground, GND
−