2.12.17.5

OU − overvoltage monitoring

This function monitors the DC bus and protects the controller.

Error

Monitoring function

System variable

Possible responses

No.

Display

TRIP

Message

Warning

FAIL−QSP

Off

x020 OU

Overvoltage

MCTRL_bOvervoltage_b

·

· Lenze setting

ü Setting possible

Monitoring is actuated if the DC bus voltage at the terminals +U

G

and −U

G

exceeds a switch−off

threshold dependent on C0173, and it remains active until the value falls below the respective
switch−on threshold again.

·

The DC−bus voltage is set under C0173:

Code

LCD

Possible settings

IMPORTANT

Lenze

Selection

[C0173] UG limit

1

Adaptation of DC−bus voltage
thresholds

·

Check during commissioning and
adapt if necessary

·

All drive components in
interconnected drives must have
the same thresholds

0

Mains < 400 V; with or without brake unit

1

Mains = 400 V; with or without brake unit

2

Mains = 460 V; with or without brake unit

3

Mains = 480 V; without brake unit

4

Mains = 480 V; with brake unit

·

The switch−off and switch−on thresholds dependent on C0173 can be gathered from the
following table:

Setting of C0173

Switch−off threshold

Switch−on threshold

0

Mains < 400 V; with or without brake unit

770 V

755 V

1

Mains = 400 V; with or without brake unit

770 V

755 V

2

Mains = 460 V; with or without brake unit

770 V

755 V

3

Mains = 480 V; without brake unit

770 V

755 V

4

Mains = 480 V; with brake unit

800 V

785 V

·

The switch−off threshold defines the voltage level of the DC−bus voltage, at which the pulse
inhibit is activated.