9300 servo plc, System blocks, 1 oc1 − short−circuit monitoring – Lenze DDS Target 9300 Servo PLC V8.x User Manual
Page 80: 2 oc2 − earth−fault monitoring
2.12
MCTRL_MotorControl (node number 131)
9300 Servo PLC
System blocks
2−74
L
9300 Servo PLC EN 5.1
2.12.17.1
OC1 − short−circuit monitoring
This monitoring function protects the drive controller.
Error
Monitoring function
System variable
Possible responses
No.
Display
TRIP
Message
Warning
FAIL−QSP
Off
x011 OC1
Short circuit
MCTRL_bShortCircuit_b
·
· Lenze setting
ü Setting possible
Monitoring is actuated in the event of a short circuit in the motor phases. This can also be caused
by an interturn fault in the machine.
·
Monitoring can also respond during power−up if an earth fault occurs.
·
If monitoring responds, the drive controller has to be disconnected from the mains and the
short circuit has to be eliminated.
2.12.17.2
OC2 − earth−fault monitoring
This monitoring function protects the drive controller.
Error
Monitoring function
System variable
Possible responses
No.
Display
TRIP
Message
Warning
FAIL−QSP
Off
x012 OC2
Earth fault
MCTRL_bEarthFault_b
·
· Lenze setting
ü Setting possible
The 9300 Servo PLC is equipped with earth−fault detection as standard.
·
If monitoring is actuated, the drive controller has to be disconnected from the mains and the
earth fault has to be eliminated.
Possible causes of an earth fault:
·
Short circuit to frame of the machine
·
Short circuit of a phase to the shield
·
Short circuit of a phase to PE