9300 servo plc, System blocks, 8 oh − heatsink temperature monitoring (fixed) – Lenze DDS Target 9300 Servo PLC V8.x User Manual
Page 90
2.12
MCTRL_MotorControl (node number 131)
9300 Servo PLC
System blocks
2−84
L
9300 Servo PLC EN 5.1
2.12.17.8
OH − heatsink temperature monitoring (fixed)
This monitoring function protects the drive controller.
Error
Monitoring function
System variable
Possible responses
No.
Display
TRIP
Message
Warning
FAIL−QSP
Off
x050 OH
Heatsink temperature (fixed)
MCTRL_bKuehlGreaterSet−
Value_b
·
· Lenze setting
ü Setting possible
MCTRL_bKuehlGreaterSetValue_b is derived from a comparator with hysteresis. The switch−off
threshold and the hysteresis are fixed:
·
The switch−off threshold is 85 °C
·
The hysteresis is 5 K, i.e. the value for switching on again is 80 ºC.
The following causes can bring about an actuation of the monitoring process:
Cause
Remedy
The ambient temperature is too high.
Mount a blower in the control cabinet.
The drive controller is overloaded in the arithmetic mean, i. e. overload
and recovery phase exceed 100%.
·
Mount a blower in the control cabinet.
·
Shorten overload phase.
·
Use a more powerful drive controller.