2.2

AIF2_IO_AutomationInterface (node number 42)

9300 Servo PLC

System blocks

2−16

L

9300 Servo PLC EN 5.1

System variables

Variable

Data type

Signal type

Address

Display code

Display

format

Note

AIF2_nInW1_a

Integer

Analog

%IW42.0

AIF2_nInW2_a

%IW42.1

AIF2_nInW3_a

%IW42.2

AIF2_nInW4_a

%IW42.3

AIF2_bInB0_b

Bool

Binary

%IX42.0.0

...

...

AIF2_bInB15_b

%IX42.0.15

AIF2_bInB16_b

%IX42.1.0

...

...

AIF2_bInB31_b

%IX42.1.15

AIF2_dnInD1_p

Double integer

Position

%ID42.0

User data

The 4 first bytes of the received 8 bytes of user data are assigned to several variables of different data
types simultaneously. Thus the data can be evaluated in the PLC program as

·

binary information (1 bit)

·

quasi−analog value (16 bits)

·

angle information (32 bits)

according to the requirements.

Byte

Variable (1 bit)

Variable (16 bits)

Variable (32 bits)

1, 2

AIF2_bInB0_b

...

AIF2_bInB15_b

AIF2_nInW1_a

AIF2_dnInD1_p

3, 4

AIF2_bInB16_b

...

AIF2_bInB31_b

AIF2_nInW2_a

5, 6

AIF2_nInW3_a

7, 8

AIF2_nInW4_a