9300 servo plc, Appendix, 6 code table – Lenze DDS Target 9300 Servo PLC V8.x User Manual
Page 135

9300 Servo PLC
Appendix
3.6
Code table
3−129
L
9300 Servo PLC EN 5.1
Code
Information
Possible settings
LCD
Code
Information
Selection
Lenze
LCD
C0128 TAU motor
5,0
Thermal time constant of the motor
The time constant is required for calculating the
I
2
× t−disconnection.
0.1
{0.1 min}
50.0
C0129 Charc.: Ix/Nx
Reduction of the speed/torque characteristic for
UL−compliant thermal motor monitoring (I
2
× t)
The reduced speed/torque characteristic reduces the
permissible thermal load of self−ventilated standard
motors.
1
100
10
{1 %}
200 S1 torque characteristic I
1
/I
rated
This value also enables an increase of the maximally
permissible utilisation.
2
40
S1 torque characteristics n
2
/n
rated
With increasing speeds, the maximally permissible
utilisation remains unchanged (I
Mot
= I
rated
).
C0135 System Var
0
Internal code
·
Control word for networking via automation interface
(AIF)
·
FCODE_bC135Bit0_b ... FCODE_bC135Bit15_b
0
{1}
65535
Decimal value is bit−coded:
Bit 00
Freely configurable 0
Bit 01
freely configurable 1
Bit 02
Freely configurable 2
Bit 03
quick stop (QSP)
Bit 04
Freely configurable 4
Bit 05
Freely configurable 5
Bit 06
freely configurable 6
Bit 07
freely configurable 7
Bit 08
Operation inhibited
Bit 09
controller inhibit (CINH)
Bit 10
TRIP set
Bit 11
TRIP reset
Bit 12
Freely configurable 12
Bit 13
Freely configurable 13
Bit 14
Freely configurable 14
Bit 15
Freely configurable 15
C0136 CTRLWORD
g
Control word
·
Hexadecimal value is bit−coded.
0
{hex}
FFFF
1
DCTRL_DriveControl
2
CAN1_IN
3
AIF1_IN
C0141 FCODE (setval)
0.00
Freely configurable code (relative analog signals)
·
FCODE_nC141_a
−199.99
{0.01 %}
199.99
C0142 Start options
1
Starting performance of the Servo PLC
·
After power−on
·
After message (t > 0.5 s)
·
After TRIP
0
Start protection
1
Automatic start