Digital_io (node number 1), Inputs_digital (digital inputs), 10 digital_io (node number 1) – Lenze DDS Target 9300 Servo PLC V8.x User Manual
Page 53: 9300 servo plc, System blocks, 1 inputs_digital (digital inputs), System variables, Electrical data of the input terminals
9300 Servo PLC
System blocks
2.10
DIGITAL_IO (node number 1)
2−47
L
9300 Servo PLC EN 5.1
2.10
DIGITAL_IO (node number 1)
2.10.1
Inputs_DIGITAL (digital inputs)
This SB reads in the signals at the terminals X5/E1 ... E5 and conditions them.
C0443
X5
Inputs_DIGITAL
1
0
C0114/1...5
E3
28
E5
E1
E4
E2
1
DCTRL-X5/28
DIGIN_bIn1_b
DIGIN_bIn2_b
DIGIN_bIn5_b
DIGIN_bIn4_b
DIGIN_bIn3_b
DIGIN_bCInh_b
Fig. 2−21
Inputs_DIGITAL
System variables
Variable
Data type
Signal type
Address
Display
code
Display
format
Note
DIGIN_bCInh_b
Bool
Binary
%IX1.0.0
−
−
Controller inhibit (CINH) acts
directly on the DCTRL control.
DIGIN_bIn1_b
%IX1.0.1
C0443
bin
DIGIN_bIn2_b
%IX1.0.2
DIGIN_bIn3_b
%IX1.0.3
DIGIN_bIn4_b
%IX1.0.4
DIGIN_bIn5_b
%IX1.0.5
Electrical data of the input terminals
Terminal
Use
Measuring range
X5/28
Controller enable (RFR)
LOW level:
HIGH level:
Input current:
0 ... +4 V
+13 ... +30 V
8 mA per input (at 24 V)
X5/E1
Interrupt−capable
1
Touch−probe−capable
2
Freely
assignable
X5/E2
X5/E3
X5/E4
TP signal, actual motor speed
X7 (resolver), X8 (encoder)
1
Response time of the interrupt task: < 250
ms
2
Use of X5/E1 ... E3 as a touch probe input:
See "Function library LenzeTpDrv.lib" manual
X5/E5
TP signal
X9 (digital frequency input)
X5/39
Ground (GND) of digital inputs and outputs
·
The terminal polarity of the inputs X5/E1 ... E5 can be configured under C0114:
Code
LCD
Possible settings
Info
Lenze
Selection
C0114 DIGIN pol
Terminal polarity
0
HIGH active
1
LOW active
1
1
X5/E1
2
1
X5/E2
3
0
X5/E3
4
0
X5/E4
5
0
X5/E5