Festo Контроллер позиционирования CPX-CMPX User Manual
Page 97
3. Installation
3−17
Festo P.BE−CPX−SYS−EN en 0902e
Separate circuits
Interlinking blocks with a 5−pin plug enable separate circuits
to be created for supplying load voltage to the outputs/
valves and for supplying operating voltage to the electronics/
sensors. Fig. 3/3 provides an overview.
1
2
3
4
CPX−(M−)GE−EV−
S−... CPX−(M−)GE−EV CPX−(M−)GE−EV−Z−...
5
0 V
val
24 V
val
0 V
OUT
24 V
OUT
0 V
el/sen
24 V
el/sen
FE
0 V
OUT
6
24 V
OUT
1
Load voltage for valves (24 V
val
and
0 V
val
)
2
Load voltage for digital outputs
(24 V
out
and 0 V
out
)
3
Operating voltage for electronics and
sensors (24 V
el/sen
and 0 V
el/sen
)
4
Functional earth (FE)
5
Rails for internal functions
6
Connection to FE connection on
end plate
Fig. 3/3:
Basic representation of the power supply concept for interlinking blocks with
5−pin alternative connections (7/8", push−pull)
The pin allocation for all alternative connections is described
in Tab. 3/4 and in the package insert for the interlinking
blocks with supply.