3. Installation

3−17

Festo P.BE−CPX−SYS−EN en 0902e

Separate circuits

Interlinking blocks with a 5−pin plug enable separate circuits
to be created for supplying load voltage to the outputs/
valves and for supplying operating voltage to the electronics/
sensors. Fig. 3/3 provides an overview.

1

2

3

4

CPX−(M−)GE−EV−

S−... CPX−(M−)GE−EV CPX−(M−)GE−EV−Z−...

5

0 V

val

24 V

val

0 V

OUT

24 V

OUT

0 V

el/sen

24 V

el/sen

FE

0 V

OUT

6

24 V

OUT

1

Load voltage for valves (24 V

val

and

0 V

val

)

2

Load voltage for digital outputs
(24 V

out

and 0 V

out

)

3

Operating voltage for electronics and
sensors (24 V

el/sen

and 0 V

el/sen

)

4

Functional earth (FE)

5

Rails for internal functions

6

Connection to FE connection on
end plate

Fig. 3/3:

Basic representation of the power supply concept for interlinking blocks with
5−pin alternative connections (7/8", push−pull)

The pin allocation for all alternative connections is described
in Tab. 3/4 and in the package insert for the interlinking