5. Diagnostics and error handling

5−29

Festo P.BE−CPX−SYS−EN en 0902e

Error numbers of error class 1

No.

Handheld texts

Operating status

Eliminating faults

200

[Fault param. transfer moĆ
dule n]

Fault in parametrisation
(parameter transfer failed)

Replace module if Power Off/
On does not remedy problem

201

[Invalid field bus address]

Address incorrect

Check the DIL switch setting,
correct if necessary

202

[Protokoll Asic not ready]

Initialisation of the Chips
protocol defective

Replace module if Power Off/
On does not remedy problem

203

[MMI serves CPX module]

MMI serves CPX modules,
parametrisation is not possiĆ
ble via the fieldbus node or
FEC

Terminate MMI access

204

[Invalid setting switch unit]

Invalid switch setting

Check the DIL switch setting,
correct if necessary

205
...
254

Reserved

255

[unknown fault]

Tab. 5/10: Possible faults (fault class 1)