Example of some channel−specific module parameters – Festo Контроллер позиционирования CPX-CMPX User Manual
Page 174
B. Parameters and data of the CPX terminal
B−20
Festo P.BE−CPX−SYS−EN en 0902e
Module parameter: Data format for analogue value of outputs
Modules
For modules with analogue outputs (see manual for the module)
Function no.
4828 + m * 64 + 3
m = module number (0 ... 47)
Description
Determines the data format with which the relevant analogue values are procesĆ
sed internally.
Bit
Bits 4, 5
Values
Data format for analogue value of outputs
See manual for the relevant analogue module
[Output format]
Note
The choice of data format depends on the fieldbus or fieldbus master used and
simplifies evaluation of the analogue values.
Tab. B/17: Data format for analogue value of outputs
Example of some channel−specific module
parameters
Module parameter: Signal extension channel x
Modules
For modules with digital inputs (see manual for the module)
Function no.
4828 + m * 64 + 6
m = module number (0 ... 47)
Description
Determines whether the signal extension for the relevant I−channel is to be
enabled or blocked.
Bit
Bit 0 ... 7 (channel 0 ... 7)
Values
Signal extension input channel ...
0 = blocked
1 = enabled
[Signal extension Inp Ch ...]
[Disabled]
[Enabled]
Note
The signal extension time can be specified separately for each module
(see function no. 4828 + n; n = m * 64 + 1).
Tab. B/18: Signal extension channel x (channel−specific)