beautypg.com

Festo Контроллер позиционирования CPX-CMPX User Manual

Page 148

background image

A. Technical appendix

A−4

Festo P.BE−CPX−SYS−EN en 0902e

Severity
level

Vibration

Shock

Continuous shock

1

0.15 mm path at 10 ... 58 Hz;
2 g acceleration at
58 ... 150 Hz

±15 g at 11 ms duraĆ
tion; 5 shocks per
direction

±15 g at 6 ms duration;
1000 shocks per direction

2

0.35 mm path at 10 ... 60 Hz;
5 g acceleration at
60 ... 150 Hz

±30 g at 11 ms duraĆ
tion; 5 shocks per
direction

Operating voltage for fieldbus interface

Ĉ Nominal value
Ĉ Tolerance

See manual for the specific CPX bus node

Caution
Short circuits can cause damage.

Provide external fuse protection for the system supply and
additional supplies. The permissible current per pin at the
supply is:

Ĉ 7/8" plug, 4−pin:

max. 10 A

1) 2)

Ĉ 7/8" plug, 5−pin:

max. 8 A

1)

Ĉ M18 plug (4−pin):

max. 16 A

2)

Ĉ Push−pull plug (5−pin):

max. 16 A

1)

Limited by the specification of the connected plug conĆ

nector. Values apply for plug connectors from Festo AccesĆ
sories. If using third−party products, comply with the appliĆ
cable specifications.

2)

Please note that with a 4−pin system supply via pin

0 V", the

sum of both currents of the operating and load

voltages flows.