5. Diagnostics and error handling

5−21

Festo P.BE−CPX−SYS−EN en 0902e

Error numbers of error class 2

No.

Eliminating faults

Operating status

Handheld display

16

[Module code incorrect]

Stored configuration is diffeĆ
rent to the actual CPX strucĆ
ture

With the CPX terminal:

·

Check the structure and reĆ
save, if necessary (for the
procedure, see secĆ
tion B.2.2, System parameĆ
ter System start)

For the CPX bus node:

·

Modify the System start
parameter to Default paĆ
rametrisation and current
CPX equipment status"

With the CPX−FEC:

·

Save the actual configuraĆ
tion as nominal configuraĆ
tion with FST software

17

[I/O length incorrect]

Saved I/O length of the moĆ
dule is different to the actual
CPX structure.

With CPX−CP interface:
Ĉ The saved string assignĆ

ment of the CPX−CP interĆ
face is not the same as the
configuration saved in the
CPX bus node or in the
CPX−FEC

With the CPX terminal:

·

Check the structure and reĆ
save, if necessary (for the
procedure, see secĆ
tion B.2.2, System parameĆ
ter System start)

For the CPX bus node:

·

Modify the System start
parameter to Default paĆ
rametrisation and current
CPX equipment status"

With the CPX−FEC:

·

Save the actual configuraĆ
tion as nominal configuraĆ
tion with FST software

18

[Address range exceeded]

Number of I/O points exceeĆ
ded

Check the DIL switch setting
or the CPX structure. See maĆ
nual for the specific CPX bus
node/CPX−FEC

19

[Life cycle exceeded]

Nominal service life/life cycle
exceeded

Replace module or spare part
(e.g. air filter)
See manual for the relevant
module