5. Diagnostics and error handling
5−21
Festo P.BE−CPX−SYS−EN en 0902e
Error numbers of error class 2
No.
Eliminating faults
Operating status
Handheld display
16
[Module code incorrect]
Stored configuration is diffeĆ
rent to the actual CPX strucĆ
ture
With the CPX terminal:
·
Check the structure and reĆ
save, if necessary (for the
procedure, see secĆ
tion B.2.2, System parameĆ
ter System start)
For the CPX bus node:
·
Modify the System start
parameter to Default paĆ
rametrisation and current
CPX equipment status"
With the CPX−FEC:
·
Save the actual configuraĆ
tion as nominal configuraĆ
tion with FST software
17
[I/O length incorrect]
Saved I/O length of the moĆ
dule is different to the actual
CPX structure.
With CPX−CP interface:
Ĉ The saved string assignĆ
ment of the CPX−CP interĆ
face is not the same as the
configuration saved in the
CPX bus node or in the
CPX−FEC
With the CPX terminal:
·
Check the structure and reĆ
save, if necessary (for the
procedure, see secĆ
tion B.2.2, System parameĆ
ter System start)
For the CPX bus node:
·
Modify the System start
parameter to Default paĆ
rametrisation and current
CPX equipment status"
With the CPX−FEC:
·
Save the actual configuraĆ
tion as nominal configuraĆ
tion with FST software
18
[Address range exceeded]
Number of I/O points exceeĆ
ded
Check the DIL switch setting
or the CPX structure. See maĆ
nual for the specific CPX bus
node/CPX−FEC
19
[Life cycle exceeded]
Nominal service life/life cycle
exceeded
Replace module or spare part
(e.g. air filter)
See manual for the relevant
module