beautypg.com

Festo Контроллер позиционирования CPX-CMPX User Manual

Page 72

background image

2. Assembly

2−28

Festo P.BE−CPX−SYS−EN en 0902e

Fit the H−rail as follows:

1. Make sure that the fastening surface can support the

weight of the CPX terminal.

2. Fit an H−rail (support rail as per EN 60715 − 35x15;

width 35 mm, height 15 mm).

3. Fasten the H−rail at least every 100 mm to the fastening

surface.

4. Hang the CPX terminal onto the H−rail. Secure the CPX

terminal on both sides with the H−rail clamping unit
against tilting or sliding down (see Fig. 2/14).

5. With a vibrating load or if the node is fitted in a sloping

position, secure the H−rail clamping unit against unintenĆ
tional loosening or opening with two locking screws
(Fig. 2/14, item 4).

1

3

2

4

1

H−rail

2

H−rail clamping unit unlocked

3

H−rail clamping unit locked

4

Retaining screw

Fig. 2/14: Top view: Fitting the valve terminal onto an H−rail