Festo Контроллер позиционирования CPX-CMPX User Manual
Page 138
5. Diagnostics and error handling
5−24
Festo P.BE−CPX−SYS−EN en 0902e
Error numbers of error class 2
No.
Eliminating faults
Operating status
Handheld display
36
[Short circuit CP line]
Short circuit in CP string
(24 V
EL/SEN
or 24 V
VAL
)
Ĉ Communication on CP
string interrupted
·
Check string assignments,
if necessary replace
CP cable
37
[Fault in controlling]
Defect with the controller
function (e.g. nominal value
cannot be reached)
Check pressure and actuator
supply
38
[Missing valve]
No valve recognised
Check valve (function/instalĆ
lation), replace if necessary
39
[Maintenance required]
Maintenance necessary
See manual for the relevant
module
40
[CO−Life Guard]
Fault resulting from
Life Guard monitoring
Check cabling, check CAN bus
load, check Guard Time and
Life Factor and adjust if neĆ
cessary
41
[CO−Heart Beat]
Fault resulting from
Heart Beat monitoring
Check cabling, check CAN bus
load, check Heart Beat Time,
adjust if necessary
42
Reserved
43
[CO−CAN Overrun (Objects
lost)]
Telegrams have been lost
Check CAN bus load
44
[CO−Invalid PDO received]
PDO received with two few
data bytes
Possibly correct PDO mapping
or increase number of PDO
bytes
45
[CO−CAN WarnLimit
reached]
Some defective CAN teleĆ
grams have been discovered
Check cabling
46
[CO−CAN recovered from
BusOff ]
Defective CAN telegrams
have been increasingly
discovered
Check cabling; a CAN particiĆ
pant may be defective
47
[CO−Bus Power lost]
No power supply at the CAN
interface
Check power supply at
24 VDC Bus and 0 V Bus
48
[Fault in Calibration]
Calibration fault (factory
adjustment missing)
Replace module