Festo Контроллер позиционирования CPX-CMPX User Manual
Page 185
B. Parameters and data of the CPX terminal
B−31
Festo P.BE−CPX−SYS−EN en 0902e
Diagnostic memory data (10 bytes per entry, max. 40 entries)
Function no.
1)
Byte
no.
Designation
Description
Value
3488 + n
1
Days [day]
Number of days
2)
0 ... 255
n = 10 * d + 0
2
Hours [h]
Number of hours
2)
0 ... 23
n = 10 * d + 1
3
Minutes [m]
Number of minutes
2)
0 ... 59
n = 10 * d + 2
4
Seconds [s]
Number of seconds
2)
0 ... 59
n = 10 * d + 3
5
Milliseconds [ms]
Number of 10 msec
2)
Additionally: Bit 7 is set if it is the
first entry after Power ON.
0 ... 99
or
128...227
n = 10 * d + 4
6
Module code
3)
Module code of the module which
registered the fault.
0 ... 255
n = 10 * d + 5
7
Module position
[Pos]
Module number of the module which
registered the fault; 63 = fault not
module−related
0 ... 47,
63
n = 10 * d + 6
8
Channel number
3)
Bit 7
6
5 ... 0:
Description
0
0
0 ... 63: No. of the 1st
faulty O channel
1
0
0 ... 63: No. of the 1st
faulty I channel
0
1
0 ... 63: Module fault
1
1
0 ... 63: Reserved
0 ... 255
n = 10 * d + 7
9
Error number [FN]
0 ... 255:
Error number (possible
error messages see
section 5.2.3)
0 ... 255
n = 10 * d + 8
10
Subsequent
channels
3)
Number of subsequent channels with
the same fault
0 ... 63
n = 10 * d + 9
1) d (diagnostic event) [NB] = 0 ... 39 ; most current diagnostic event = 0;
2) Measured from the moment the power supply is switched on
3) If the fault number = 0, the content of these bytes is also 0. If the fault number lies
between 128 ... 199 (error class 3), the content of these bytes is not relevant (servicing required).
Tab. B/37: Diagnostic memory data