B. Parameters and data of the CPX terminal
B−10
Festo P.BE−CPX−SYS−EN en 0902e
System parameter: Fail safe (reaction to communication faults)
Function no.
4402
Description
Determines the signal status which the outputs/valves are to assume in the
event of fieldbus communication faults, e.g. in the event of:
Ĉ Communication failure (fieldbus interruption, PLC/IPC failure)
Ĉ Communication stop.
In the following case, the channel−orientated Fail Safe settings (module paraĆ
meters Fault mode and Fault state) are reset automatically for safety reasons in
order to avoid undesired signal states.
Ĉ When changing from Assume fault mode" to Reset all outputs" or to Hold
last state".
Bit
Bits 0, 1
Values
Bit 1 0
0 0
Fail safe
Description
Reset all outputs (presetting)
[Fail safe]
[Reset outputs]
0 1
Hold last state (retain signal status)
[Hold last state]
1 0
Assume fault mode
[Assume fault mode]
Note
The Fault mode status is set with the channel−specific module parameters.
Further information on this parameter can be found in section C.3.
Tab. B/5: Fail safe