C. General information on parametrisation

C−16

Festo P.BE−CPX−SYS−EN en 0902e

System parameters

Settings

Description

Fail safe

Reset outputs
(presetting)

Reset all outputs/valves

Hold last state

Retain current signal status for all outputs/
valves

Assume Fault mode
value

Accept the signal status defined for the relevant
channel

Tab. C/4: System parameter Fail safe"

If Accept fault mode value" is activated, the signal states
defined by module parameter for the relevant channel will
become effective (see Fig. C/8).

Module parameters

Settings

Description

Fault mode

Hold last state

Retain current signal status

Fault state
(presetting)

Accept the signal status defined by Fault state

Fault state
Ĉ Digital signal

Reset output
(presetting)

Reset output signal (output/valve)

Set output

Set output signal (output/valve)

Ĉ Analogue signal

Analogue value

Value of the analogue signal

Tab. C/5: Module parameters Fault mode and Fault state

Mode of operation

The Fault mode" parameter is used to determine whether
the current signal status is to be retained or whether the
signal status defined by Fault state" is to be accepted.