beautypg.com

Festo Контроллер позиционирования CPX-CMPX User Manual

Page 134

background image

5. Diagnostics and error handling

5−20

Festo P.BE−CPX−SYS−EN en 0902e

Error numbers of error class 2

No.

Handheld display

Operating status

Eliminating faults

0

[No error]

No fault

1

[General diagnosis]

General diagnosis (module−
specific error)

See manual for the relevant
module

2

[Short circuit]

Short circuit/overload in senĆ
sor supply (SCS) or at output
(SCO)

Eliminate short circuit/overĆ
load (see manual for the speĆ
cific module)

3

[Wire fracture/idling curĆ
rent I/O]

Wire fracture/idling at current
input/output

Check and, if necessary, reĆ
place the cable and connecĆ
ted sensors/actuators.

4

[Short circuit in actuator
supply]

Failure of load voltage supply
due to short circuit/overload
(on output side)

Check connected actuators
as well as their connections

5

[Undervoltage in power
supply]

Undervoltage in power supply
(on input side)

Eliminate undervoltage at
system supply or additional
supply (see Tab. 3/4 for pin
assignment)

6 ... 8

Reserved

9

[Lower limit exceeded]

Fall below rated range

Check signal area and paraĆ
meterised limit

10

[Upper limit exceeded]

Rated range exceeded

Check signal area and paraĆ
meterised limit

11

[Short circuit valve]

Short circuit at valve

Check valve and pneumatic
interface

12

Reserved

13

[Wire fracture (open load)]

Wire fracture at valve (open
load)

Check valve and pneumatic
interface

14

[Condition counter exceeĆ
ded]

Limit value of the condition
counter exceeded

Set or delete the limit value of
the condition counter by paraĆ
meterising

15

[Module/channel failure]

Module/channel failed

Check module (function/inĆ
stallation), replace if necesĆ
sary