5. Diagnostics and error handling
5−20
Festo P.BE−CPX−SYS−EN en 0902e
Error numbers of error class 2
No.
Handheld display
Operating status
Eliminating faults
0
[No error]
No fault
−
1
[General diagnosis]
General diagnosis (module−
specific error)
See manual for the relevant
module
2
[Short circuit]
Short circuit/overload in senĆ
sor supply (SCS) or at output
(SCO)
Eliminate short circuit/overĆ
load (see manual for the speĆ
cific module)
3
[Wire fracture/idling curĆ
rent I/O]
Wire fracture/idling at current
input/output
Check and, if necessary, reĆ
place the cable and connecĆ
ted sensors/actuators.
4
[Short circuit in actuator
supply]
Failure of load voltage supply
due to short circuit/overload
(on output side)
Check connected actuators
as well as their connections
5
[Undervoltage in power
supply]
Undervoltage in power supply
(on input side)
Eliminate undervoltage at
system supply or additional
supply (see Tab. 3/4 for pin
assignment)
6 ... 8
Reserved
9
[Lower limit exceeded]
Fall below rated range
Check signal area and paraĆ
meterised limit
10
[Upper limit exceeded]
Rated range exceeded
Check signal area and paraĆ
meterised limit
11
[Short circuit valve]
Short circuit at valve
Check valve and pneumatic
interface
12
Reserved
13
[Wire fracture (open load)]
Wire fracture at valve (open
load)
Check valve and pneumatic
interface
14
[Condition counter exceeĆ
ded]
Limit value of the condition
counter exceeded
Set or delete the limit value of
the condition counter by paraĆ
meterising
15
[Module/channel failure]
Module/channel failed
Check module (function/inĆ
stallation), replace if necesĆ
sary