Module parameter: Monitoring of the CPX module

Modules

Depending on the monitoring function for modules with digital and analogue
inputs and outputs (see description on the respective module)

Function no.

4828 + m * 64 + 0

m = module number (0 ... 47)

Description

Monitoring of the possible faults can be activated or deactivated (suppressed)
for each module independently. Active monitoring causes the following. The
fault is:
Ĉ Sent to the CPX bus node
Ĉ Displayed by the module common error LED.

Bit

0

Monitoring
Description
Short circuit/overload in sensor supply (SCS)

[Monitor]

[Monitor SCS]

1

Short circuit/overload at the outputs (SCO)

[Monitor SCO]

2

Undervoltage of outputs/valves (V

OUT/VAL

)

[Monitor Vout/val]

3

Short circuit at the valve (SCV)

[Monitor SCV]

4

Reserved

5

Reserved

6

Reserved

7

Monitoring parametrisation faults

[Monitor parameters]

Values

1 = active (presetting)
0 = inactive

[Active]
[Inactive]

Note

Monitoring can also be set for the complete CPX terminal (see System parameĆ
ter monitoring").

Tab. B/12: Monitoring the CPX module

For parametrising the Monitoring CP modules" on the
CPX−CP interface see the manual for the CPX−CP interface
type P. BE−CPX−CP−....