B. Parameters and data of the CPX terminal
B−16
Festo P.BE−CPX−SYS−EN en 0902e
Module parameter: Monitoring of the CPX module
Modules
Depending on the monitoring function for modules with digital and analogue
inputs and outputs (see description on the respective module)
Function no.
4828 + m * 64 + 0
m = module number (0 ... 47)
Description
Monitoring of the possible faults can be activated or deactivated (suppressed)
for each module independently. Active monitoring causes the following. The
fault is:
Ĉ Sent to the CPX bus node
Ĉ Displayed by the module common error LED.
Bit
0
Monitoring
Description
Short circuit/overload in sensor supply (SCS)
[Monitor]
[Monitor SCS]
1
Short circuit/overload at the outputs (SCO)
[Monitor SCO]
2
Undervoltage of outputs/valves (V
OUT/VAL
)
[Monitor Vout/val]
3
Short circuit at the valve (SCV)
[Monitor SCV]
4
Reserved
−
5
Reserved
−
6
Reserved
−
7
Monitoring parametrisation faults
[Monitor parameters]
Values
1 = active (presetting)
0 = inactive
[Active]
[Inactive]
Note
Monitoring can also be set for the complete CPX terminal (see System parameĆ
ter monitoring").
Tab. B/12: Monitoring the CPX module
For parametrising the Monitoring CP modules" on the
CPX−CP interface see the manual for the CPX−CP interface
type P. BE−CPX−CP−....