5. Diagnostics and error handling
5−23
Festo P.BE−CPX−SYS−EN en 0902e
Error numbers of error class 2
No.
Eliminating faults
Operating status
Handheld display
28
[Alarm value reached]
Alarm value reached
Check operating conditions
See manual for the relevant
module
29
[Fault in parametrizing]
Fault in parametrisation
Check the parametrisation
undertaken and, if necessary,
undertake the parametrisaĆ
tion again with the correct
parameters.
30
[No new output data
(slave)]
Fault in internal communicaĆ
tion (no new output data)
Replace module if Power Off/
On does not remedy problem
31
[No bus connection (slave)]
Bus connection interrupted
Make bus connection or
check configuration
32
[No STI read access (slave)]
STI read access defective
Repeat STI read access
33
[No parameter access
(slave)]
Read access parameter deĆ
fective
Repeat read access parameĆ
ter
34
[CP module lost / fault]
Ĉ Incorrect string assignment
ascertained during operaĆ
tion (e.g. CP module failed
or CP cable defective)
Ĉ More than one module faiĆ
led during operation ć
modules are no longer
recognised.
·
Check CP strings (CP moduĆ
les and CP cables), if neĆ
cessary replace CP moduĆ
les or CP cables
·
Switch power supply off
and then on again. If fault
still occurs, check and, if
necessary, replace CP caĆ
bles and CP modules
35
[CP configuration failure]
Ĉ When the power supply is
switched on, the string asĆ
signment does not match
the saved string assignĆ
ment
Ĉ Incorrect module recogniĆ
sed during operation (diffeĆ
rent type, see manual for
CPX−CP interface)
·
Check CP strings (CP moduĆ
les and CP cables), if neĆ
cessary replace CP moduĆ
les or CP cables
·
With correct string assignĆ
ment: String assignment
must be saved or (see maĆ
nual for CPX−CP interface)
·
Check string assignment, if
necessary replace CP moĆ
dule