Festo Контроллер позиционирования CPX-CMPX User Manual
Page 142
5. Diagnostics and error handling
5−28
Festo P.BE−CPX−SYS−EN en 0902e
Error numbers of error class 3
No.
Eliminating faults
Operating status
Handheld texts
138
[CBUS init fault (gap)]
Fault in internal configuration
Check module array (there
must not be any configuration
gaps in the CPX terminal)
139
[Order queue full]
Fault in internal communicaĆ
tion
Check CPX terminal and,
if necessary, replace
140
[CBUS−EEPROM error]
Hardware defective
Replace module
141
[CBUS C−timeout error]
Fault in internal communicaĆ
tion
Check CPX terminal and,
if necessary, replace
142
[CBUS telegram fault]
Fault in internal communicaĆ
tion
Check CPX terminal and,
if necessary, replace
143
[BIU access error]
System error has occurred
Replace module if Power Off/
On does not remedy problem
144
[Licence error]
Module does not have a valid
licence
Procure licence, if necessary
replace module
145
...
149
Reserved
150
[NETOS fatal error]
System error has occurred
Replace module if Power Off/
On does not remedy problem
151
...
199
Reserved
Tab. 5/9: Possible faults (fault class 3)