3. Installation
3−14
Festo P.BE−CPX−SYS−EN en 0902e
Interlinking block with
additional power supply
for valves
Types CPX−GE−EV−
V...
These interlinking blocks enable separate circuits to be
created for supplying load voltage to the valves. The load
voltage for the valves, which is also supplied via an M18 or
7/8" plug, can be switched off separately. This interlinking
block must also always be placed to the right of a system
supply.
The use of interlinking blocks with additional supply for
valves causes the following (see also Fig. 3/2):
ć
The load voltage for the valves will be interrupted at the
previous module on the left.
ć
The load voltage supplied is available for the following
modules:
ć
Subsequent pneumatic modules/valves to the right
ć
CP modules that are connected to the fitted CPX−CP
interface and to those CPX−CP interfaces subsequently
fitted to the right
ć
The operating and load voltage supplies for the electric
outputs will be transmitted further.
ć
These additional supplies must not be used for MPA
pneumatics with MPA electronic modules of the type
VMPA...−FB−EM
S−... (see description of P.BE−MPA−ELEKĆ
TRONIK−...).
Interlinking blocks with
push−pull
forwarding
function of type CPX−
M−GE−EV−S−PP−5POL
These interlinking blocks are used to forward the power
supply to subsequent external equipment.
These interlinking blocks must be placed directly to the right
of a system supply and must not be used more than once
within a CPX terminal. They must not be combined with an
additional supply, either.