3. Installation
3−15
Festo P.BE−CPX−SYS−EN en 0902e
Caution
Damage to device and the environment
CPX terminals with push−pull forwarding function must
have external fuse protection to 16 A in order to avoid
overloading and resultant damage to the device and its
environment.
The use of interlinking blocks with forwarding function for
supplying power to subsequent equipment causes the followĆ
ing (see also Fig. 3/2):
ć
The operating voltage supply and the load voltage
supply are forwarded/connected through to subseĆ
quent equipment via the push−pull connection. This
replaces a T−adapter in the field.
ć
The operating voltage supply and the load voltage
supply are available to the fitted output module and
subsequent output modules to the right.
ć
Interlinking blocks with a push−pull forwarding funcĆ
tion are identically constructed to those with a push−
pull system power supply
Interlinking blocks
without
supply
Types CPX−(M−)GE−EV
These interlinking blocks serve for the electrical linking of
modules which do not require a separate load voltage
supply.