Caution
Short circuits can cause damage.

Provide external fuse protection for the system supply and
the additional supplies. The permissible current per pin at
the supplies is:

Ĉ 7/8" plug, 4−pin:

max. 10 A

1) 2)

Ĉ 7/8" plug, 5−pin:

max. 8 A

1)

Ĉ M18 plug (4−pin):

max. 16 A

2)

Ĉ Push−pull plug (5−pin):

max. 16 A

1)

Limited by the specification of the connected plug conĆ

nector. Values apply for plug connectors from Festo AccesĆ
sories. If using third−party products, comply with the appliĆ
cable specifications.

2)

Please note that with a 4−pin system supply via pin

0 V", the

sum of both currents of the operating and load

voltages flows.

Additional supply (optional) for outputs type CPX−(M−)GE−EV−Z...
Current consumption of load voltage supply outputs

Current consumption of all simultaneously activated
electric outputs that are supplied via the additional supĆ
ply (internal consumption at logic 1)

1)

_____ x _____A

Load current of simultaneously activated outputs supĆ
plied via the additional supply

+ _____ A

Current consumption of the technology modules supĆ
plied

2)

+ _____ A

Sum of the current consumption of the load voltage

= _____ A

+ ______ A

Total current consumption of the additional supply

= ______ A

1)

For the internal consumption at logical 1, see technical data for the output module

2)

Including further modules and components supplied via the technology module

Tab. 3/2: Table for calculating the current consumption of the additional supply for the