beautypg.com

Festo Контроллер позиционирования CPX-CMPX User Manual

Page 207

background image

C. General information on parametrisation

C−9

Festo P.BE−CPX−SYS−EN en 0902e

Force

Fail safe

Idle mode

Idle mode channel X

Reset outputs

0

1

0

Idle mode

Assume idle mode

Holdlaststate

Memory card

Fail safe channel X

Reset outputs

0

1

0

Fail safe

Assume fault mode

Holdlaststate

0 1

Force channel X

Force mode

enable

disable

1

disable

Idle mode is only
relevant for
certain fieldbus
protocols

Output signal (e.g. over fieldbus)

Memory card

System parameters

Module parameters

Module parameters

Module parameters

System parameters

System parameters

Output

Yes

No

Yes

No

Fieldbus communication fault

Idle mode status

1

Status LED of the respective output

Fig. C/4:

Influencing output signals