background image

B. Parameters and data of the CPX terminal

B−22

Festo P.BE−CPX−SYS−EN en 0902e

Module parameter: Idle mode channel x

Modules

For modules with digital and analogue outputs (see manual for the module)

Function no.

Access to these module parameters is made via protocol−specific functions (see
the CPX bus node description).

Description

Only relevant for certain fieldbus protocols.
Idle mode channel x:

Hold last state
Idle state (presetting)

Idle state channel x:

Set output
Reset output (presetting)

Note

With the aid of Idle mode parametrisation, the signal status which the outputs/
valves are to assume during a change into the Idle status can be determined
(see also section C.3.3).

Tab. B/21: Idle mode channel x (channel−specific)

Module parameter: Force channel x

Modules

For modules with digital and analogue inputs and outputs (see manual for the
module)

Function no.

Access to these module parameters is made via protocol−specific functions (see
the CPX bus node description).

Description

Force mode of inputs channel x:

blocked (presetting)
Force state

Force state of inputs channel x:

Set signal
Reset signal (presetting)

Force mode of outputs channel x: blocked (presetting)

Force state

Force state of outputs channel x:

Set signal
Reset signal (presetting)

Note

The function Force permits the manipulation of signal states independent of
actual operating conditions (see also section C.3.1).

Tab. B/22: Force channel x (channel−specific)