beautypg.com

3 error numbers, Error numbers – Festo Контроллер позиционирования CPX-CMPX User Manual

Page 133

background image

5. Diagnostics and error handling

5−19

Festo P.BE−CPX−SYS−EN en 0902e

5.2.3

Error numbers

Detailed information on module−specific diagnosis can be
found in the manual for the relevant module.

Possible faults of the CPX terminals are divided into three
error classes with different priority depending on the seriousĆ
ness of the fault. If a fault occurs, the system error LED
(SF LED) will flash depending on the error class.

Error class

Flashing sequence of the
SF LED

Error weighting

Priority

1

1 * flashes, pause time

Simple (e.g. simple user fault)

low

2

2 * flashes, pause time

Medium (standard diagnosis
and extended diagnosis)

medium

3

3 * flashes, pause time

High (hardware fault/internal
fault)

high

Tab. 5/7: Error classification

If several errors occur together, the error with the highest
priority will have precedence. This means that:

ć

The system error LED flashes according to the higher
priority

ć

The number of the error with the higher priority will be
entered in the system diagnostic data under function
number 1938 (error number).

Within an error class, errors of modules with a lower module
number have higher priority, e.g. errors of module number 0
have the highest priority within a specific error class. Errors of