Festo Контроллер позиционирования CPX-CMPX User Manual
Page 180
B. Parameters and data of the CPX terminal
B−26
Festo P.BE−CPX−SYS−EN en 0902e
Diagnostic memory parameter: Fault end filter
Function no.
3484
Description
Diagnostic memory filter with which you can determine whether running faults
are to be registered or not.
Bit
Bit 3
Values
Bit 3
0
1
Fault end filter
Description
Register running faults (end of fault) (filter inactive,
presetting)
Do not register running faults (end of fault) (filter
active)
[Fault end filter]
[Rec. outg. faults]
[Do not rec. outg. faults]
Note
By registering the outgoing fault, you can ascertain how long the fault has
existed. Incoming and running faults each represent one entry. With running
faults the fault number 0" is entered. Maximum 40 entries are saved together.
Tab. B/27: Fault end filter
Diagnostic memory parameter: Error number filter
Function no.
3484
Description
With this diagnostic memory filter you can:
Ĉ Suppress the registering of a desired fault message
Ĉ Register exclusively a desired fault message
Bit
Bits 4, 5
Values
Bit 5 4
0 0
0 1
1 0
1 1
Error number filter
FN = error number
Description
Error number filter inactive (presetting)
Register only defined FN
Do not register defined FN
Reserved
[Fault numbers filter]
[Inactive]
[Rec. only def. FN]
[Do not rec. def. FN]
−
Note
The error number is determined by means of the diagnostic memory parameter
Error number" (function no. 3487).
Tab. B/28: Error number filter