B. Parameters and data of the CPX terminal

B−12

Festo P.BE−CPX−SYS−EN en 0902e

System parameter: System Idle mode

Function no.

4402

Description

Establishes which signal status outputs/valves are to assume when the CPX
terminal switches into the Idle state.
In the following case, the channel−orientated Idle mode settings (module paraĆ
meters Idle mode and Idle state) are reset automatically for safety reasons in
order to avoid undesired signal states.
Ĉ When changing from Idle fault mode" to Reset all outputs" or to Hold last

state".

Bit

Bits 4, 5

Values

Bit 5 4

0 0

System Idle mode
Description
Reset all outputs (presetting)

[Idle mode]

[Reset outputs]

0 1

Hold last state (retain signal status)

[Hold last state]

1 0

Assume Idle mode

Assume idle mode]

Note

Only relevant for certain fieldbus protocols Explanations on this can be found in
the manual for the relevant CPX bus node.

Tab. B/7: Idle mode