5. Diagnostics and error handling

5−6

Festo P.BE−CPX−SYS−EN en 0902e

5.1.2

CPX−specific LEDs

PS (power system) ć power sensor/logic supply

LED (green)

Sequence

Status

Meaning / error handling

LED lights up

ON

OFF

No error. Operating volĆ
tage/sensor supply applied

ć

LED flashes

ON

OFF

Operating voltage/sensor
supply outside the toleĆ
rance range

Eliminate undervoltage

LED flashes

ON

OFF

Internal fuse for the operaĆ
ting voltage/sensor supply
has responded.

1. Eliminate short circuit/overload on

module side.

2. Depends on the parametrisation of

the module (module parameter):

·

The sensor supply voltage will be
switched on again

automatically

after the short circuit has been
eliminated (default)

·

Power Off/On is necessary

LED is off

ON

OFF

The operating voltage/senĆ
sor supply is not applied

Check the operating voltage connecĆ
tion of the electronics

PL (Power Load) ć power load supply (outputs/valves)

LED (green)

Sequence

Status

Meaning / error handling

LED lights up

ON

OFF

No error. Load voltage apĆ
plied

No

LED flashes

ON

OFF

Load voltage at the system
supply or additional supply
outside the tolerance
range

Eliminate undervoltage