5. Diagnostics and error handling
5−6
Festo P.BE−CPX−SYS−EN en 0902e
5.1.2
CPX−specific LEDs
PS (power system) ć power sensor/logic supply
LED (green)
Sequence
Status
Meaning / error handling
LED lights up
ON
OFF
No error. Operating volĆ
tage/sensor supply applied
ć
LED flashes
ON
OFF
Operating voltage/sensor
supply outside the toleĆ
rance range
Eliminate undervoltage
LED flashes
ON
OFF
Internal fuse for the operaĆ
ting voltage/sensor supply
has responded.
1. Eliminate short circuit/overload on
module side.
2. Depends on the parametrisation of
the module (module parameter):
·
The sensor supply voltage will be
switched on again
automatically
after the short circuit has been
eliminated (default)
·
Power Off/On is necessary
LED is off
ON
OFF
The operating voltage/senĆ
sor supply is not applied
Check the operating voltage connecĆ
tion of the electronics
PL (Power Load) ć power load supply (outputs/valves)
LED (green)
Sequence
Status
Meaning / error handling
LED lights up
ON
OFF
No error. Load voltage apĆ
plied
No
LED flashes
ON
OFF
Load voltage at the system
supply or additional supply
outside the tolerance
range
Eliminate undervoltage