5. Diagnostics and error handling

5−25

Festo P.BE−CPX−SYS−EN en 0902e

Error numbers of error class 2

No.

Eliminating faults

Operating status

Handheld display

49

[Lower drop out signal]

Current loop is in the lower
drop−out range

Check the installation/paraĆ
metrisation of the actuator
See manual for the relevant
module

50

[Upper drop out signal]

Current loop is in the upper
drop−out range

Check the installation/paraĆ
metrisation of the actuator
See manual for the relevant
module

51

[Sensor limit exceeded]

Physical limit for a sensor exĆ
ceeded
Ĉ Process value invalid
Ĉ Possible hardware damage

Ĉ Check structure (comĆ

pliance with module speciĆ
fication)

Ĉ Check module for damage,

if necessary replace

52

[Short circuit cold junction
comp.]

Short circuit at cold junction
compensation

Eliminate short circuit or
check connected CJC sensors

53

[Open load cold junction
comp.]

Wire break at cold junction
compensation

Check and, if necessary, reĆ
place the cable and connecĆ
ted KSK sensors

54

[Calibration data incorrect]

Calibration data is faulty

Replace module

55

[Invalid process value]

Formation of the process vaĆ
lue is invalid due to faulty
structure

Check structure (compliance
with module specification)

56 ...
63

Reserved

64

[Number of Modules incorĆ
rect]

The number of modules in the
current CPX equipment status
does not equal the saved
equipment status

Correct module equipment
status or save new one

65 ...
69

Reserved

70

[CC−L: Station equip. status
incorrect]

CPX equipment status is
greater than the number of
stations set

Check DIL switch setting
(increase number of stations)

71

[CC−L: Bus connection lost]

Bus connection interrupted

Check cabling