B. Parameters and data of the CPX terminal

B−35

Festo P.BE−CPX−SYS−EN en 0902e

Module diagnostic data: Number of the first faulty channel

Function no.

2008 + m * 4 + 0;

m = module number (0 ... 47)

Description

Specifies the number of the faulty channel (bits 0...5)

Bit

Bit 7

6

5 ... 0

: Description

0

0

0 ... 63 : No. of the 1st faulty O channel

1

0

0 ... 63 : No. of the 1st faulty I channel

0

1

0 ... 63 : Module error

1

1

0 ... 63 : Reserved

Values

Bits 0...5 : 0...63

(channel number)

Bit 6

: 0...1

Bit 7

: 0...1

Note

With the aid of the module number of the faulty module (see system diagnostic
data, byte address 1937) you can ascertain the function numbers of the relevant
diagnostic data.

Tab. B/43: Number of the first faulty channel

Module diagnostic data: Module error number

Function no.

2008 + m * 4 + 1;

m = module number (0 ... 47)

Description

Error number

Bit

Bit 0 ... 7 : error number

Values

0 ... 255

(error number)

Note

See section 5.2.3 for possible error messages.

Tab. B/44: Module error number

Module diagnostic data: Information 2 (reserved)

Function no.

2008 + m * 4 + 2;

m = module number (0 ... 47)

Description

Reserved