Festo Контроллер позиционирования CPX-CMPX User Manual
Page 189
B. Parameters and data of the CPX terminal
B−35
Festo P.BE−CPX−SYS−EN en 0902e
Module diagnostic data: Number of the first faulty channel
Function no.
2008 + m * 4 + 0;
m = module number (0 ... 47)
Description
Specifies the number of the faulty channel (bits 0...5)
Bit
Bit 7
6
5 ... 0
: Description
0
0
0 ... 63 : No. of the 1st faulty O channel
1
0
0 ... 63 : No. of the 1st faulty I channel
0
1
0 ... 63 : Module error
1
1
0 ... 63 : Reserved
Values
Bits 0...5 : 0...63
(channel number)
Bit 6
: 0...1
Bit 7
: 0...1
Note
With the aid of the module number of the faulty module (see system diagnostic
data, byte address 1937) you can ascertain the function numbers of the relevant
diagnostic data.
Tab. B/43: Number of the first faulty channel
Module diagnostic data: Module error number
Function no.
2008 + m * 4 + 1;
m = module number (0 ... 47)
Description
Error number
Bit
Bit 0 ... 7 : error number
Values
0 ... 255
(error number)
Note
See section 5.2.3 for possible error messages.
Tab. B/44: Module error number
Module diagnostic data: Information 2 (reserved)
Function no.
2008 + m * 4 + 2;
m = module number (0 ... 47)
Description
Reserved
Tab. B/45: Information 2 (reserved)