11.2 Error messages and actions

KEW6315

- 160 -

Message

Detail & Action

New sensor is detected.

Recheck the basic setting for SET

UP before measurements.

● The connected Clamp sensors are not the same ones used

during the previous test. Modify the settings of clamp sensor

directly from the “Basic setting” or press the “Detect” key.

Sensor connection is not correct.

Check the connected sensor(s).

● Appropriate current sensor may not be connected to the measure-

ment channels. Check the wiring configuration and the connected

sensor.

Out of SD card space.

Recording will be stopped.

● First, stop the recording. Confirm “Recording stopped.” message

appears, and then disappears. Backup the data file to PC or any

other medias, and then delete files or format. When using another

SD card, it should be formatted on KEW6315, not on the PC.

See “To delete, transfer or format the recorded data” (

P.

82).

Out of internal memory space.

Recording will be stopped.

● First, stop the recording. Confirm “Recording stopped.” message

appears, and then disappears. Backup the data file to PC or SD

cards, and then delete files or format.

See “To delete, transfer or

format the recorded data” (

P.

82).