KEW6315
Displaying measured flicker values in list form
KEW6315
- 120 -
Displaying measured flicker values in list form
Press the
(Flicker) Key.
Press the
Key to change the displays: V: List display/ Pst(1min): Trend graph/
Plt: Transitional change.
If variable loads, such as arc furnace, are connected, voltages may vary and cause changes in illumination
levels. Such phenomenon is called as “voltage flicker” and its severity level is indicated by “Pst” and “Plt”.
Items displayed on the LCD
Time left
Counted down time until a Pst calculation completes. Usually it takes about 10 min.
V
Phase voltage * For 3P3W and 3P3W3A, rms line voltages are displayed.
f
Frequency
Pst,1min
Severity of short term (1 min) flicker. It is useful for power quality survey or study.
Pst
Severity of short term (10 min) flicker.
Pst,MAX
Max Pst recorded through the beginning to the end of measurement. It is refreshed
every time when the measured values exceed the previous max values.
Plt
Severity of long term (2 hours) flicker.
Plt,MAX
Max Plt recorded through the beginning to the end of measurement. It is refreshed
every time when the measured values exceed the previous max values.
”Event”
Press the
(Event) Key to display the recorded events. Please refer to “Displaying recorded
events” (P. 116) in this manual.