TANK SENTINEL

®

INSTALLATION GUIDE

Probable cause – wrong cable used, wiring error, faulty wiring, or defective probe
(also generated if the unit cannot read level).

Volume Error
VOLUME ERROR was encountered while calculating product volume.
Probable cause – error in tank shape data, error in programming probe type, or
error in programming special probe (also generated if the unit cannot read level).

Water Volume Error
WATER VOLUME ERROR occurred while calculating water volume.
Probable cause – error in tank shape data, error in programming probe type, or
error in programming special probe (also generated if the unit cannot read level.

Ullage Error
ULLAGE ERROR was encountered while calculating ullage.
Probable cause – error in tank shape data, error in programming probe type, or
error in programming special probe. Also generated if the unit cannot read level.

Table Error
STRAP TABLE ERROR occurred in tank correction.
Probable cause – tank correction input out of range, or values programmed
incorrectly.

Net Error
NET VOLUME ERROR was encountered while calculating net volume.
Probable cause – error in tank shape data, error in programming probe type, error
in programming special probe, or temperature compensation not programmed
correctly.

Memory Error
MEMORY ERROR the system has encountered a CRC memory checking error.
Probable cause – setup program lost because of a dead memory backup battery
or severe power quality problem (or a new EPROM upgrade chip was installed)
Float Height
FLOAT HEIGHT ERROR due to incorrect float height / level measurement error.
Probable cause – the FLOAT TYPE (type of float) was programmed incorrectly.

Unstable Probe
UNSTABLE PROBE the probe signal has become unstable.