beautypg.com

Product level measurement – values – Franklin Fueling Systems Tank Sentinel (TS-1001, 2001, 504, 508 & 750) Installation User Manual

Page 25

background image

3

Page

3 - 2

TANK SENTINEL

®

INSTALLATION GUIDE

Figure 3-2.

Typical Tank – Fill & Probe on the Same Side of the Tank Center

Product Level Measurement – values

You must measure the product level at two points in the tank to determine the
degree to which it is tilted. A level measurement is made at the fill pipe (drop tube)
and at the location where the level probe will be installed. Record these level
measurements for each tank in the spaces provided below.

The tank must have liquid in it before these measurements are taken. If a tank is
empty, collect all of the other data until the tank has been at least partially filled,
and then take these level measurements.

Level at:

FILL (LF)

PROBE (LP)

FILL (LF)

PROBE (LP)

TANK 1

TANK 2

TANK 3

TANK 4

TANK 5

TANK 6

TANK 7

TANK 8

The blank fields for tanks 5 though 8 are for Tank Sentinel

®

consoles, Model

numbers: TS-2001 and TS-508 only (this is true throughout this manual).

NOTE

WATER

LENGTH OF TANK

Fill

" XP "

" XF "

AIR

FUEL

FUEL

PRODUCT

LEVEL

Tank

shown

tilted

Fill & Probe on

the same side of

the tank

Product / Water

Offset =

CENTER OF TANK

level

Probe

" LP "

Level

at Probe

L

C

TANK
DIAMETER

" LF "

Level

at Fill

(LF - LP) * XP

XP - XF

DROP TUBE

TOP OF TANK