Franklin Fueling Systems Tank Sentinel (TS-1001, 2001, 504, 508 & 750) Installation User Manual
Page 26

TANK MEASUREMENTS
Page
3 - 3
3
Distance from Fill to Center-line – “ XF ” values
Carefully measure the distance between the center of the Fill tube and the center of
the tank. We call this distance “ XF.” Record the distance between these two
points for each tank in the spaces provided below.
“ XF ”
“ XF ”
TANK 1
TANK 2
TANK 3
TANK 4
TANK 5
TANK 6
TANK 7
TANK 8
Distance from Probe to Center-line – “ XP ” values
Carefully measure the distance between the center of the opening where the level
probe will be installed and the center of the tank. We call this distance “ XP.”
Record the distance between these two points for each tank in the spaces provided
below.
“ XP ”
“ XP ”
TANK 1
TANK 2
TANK 3
TANK 4
TANK 5
TANK 6
TANK 7
TANK 8
Calculating Tank Tilt
Water Offset
Stick the tank to ensure that there is no water present. The water offset in the ATG
setup programming can be used to “zero” the water level reading of the ATG.
Typically, a small negative number in the water offset is needed to zero the water
float ...be sure to program the gradient before figuring out the water offset.
Product Offset
See next page. Fill in the blank equations with the appropriate & correct values for
each tank. Perform the mathematical operations indicated in the formula used to
calculate the tank tilt offset for every tank. Write the answers in the blank spaces.
Avoid errors... use a calculator and double-check all calculations. Keep all positive
and negative (+/– sign) values... offsets can be either positive or negative.
NOTE